BOS-PRD-0304.900902

quality and protecting public health. Frequent testing for these faecal indicators is still the most sensitive and

specific way of assessing the quality of potable water.

H

ydroc

a

r

b

ons

Test for hydrocarbons is conducted due to the potential for cross contamination with fuel and oil.

C

hl

orides

Legislative limits <250 mgCl/l.

Test for chlorides is conducted due to the potential for cross contamination with sea water.

T

o

ta

l V

i

ab

l

e Coun

t

(

TV

C)

The original guideline for acceptable levels of bacterial contamination in mains/drinking water was laid down

by the World Health Organisation (WHO) to be no more than 100 cfu/ml at 22°C and 10 cfu/ml at 37°C.

WHO now consider this to be an unrealistic restriction and suggests that the TVC trend is monitored for any

abnormal change.

For an indication of the general condition of the water, a TVC at 22°C and 37°C check will be taken on each

sample. The results should show

no

ab

nor

m

a

l

c

h

a

nge

.

In order to measure this, the results

should

be trended and analysed with reference to the historical levels

achievable within that vessel, Company or area, depending on the information available.

L

egione

ll

a

The danger of infection caused by Legionella bacteria is caused when it gains entry to the respiratory

system. This can occur from water suspended in air in the form of a fine mist as created by showers or tap

sprays.

Maintenance of cargo potable water tanks, pipe work, pumps and hoses as defined in these guidelines

should

control any contamination by Legionella in the water carried.

Should

an operator require cargo potable water to be tested for Legionella the following test limit applies:

T

es

t

L

i

m

i

t

Legionella <

10

3

cfu/l (cfu = colony forming units).

If the level of alert is > 10

3

cfu/l, vessel will need to:

x

Verify the origin of the deviation compared to the results obtained previously;

x

Strengheting the hygienic measures and controls.

If the level of alert is > 10

4

cfu/l, the vessel will need to:

x

Schedule a technical intervention to eliminate the risks: prohibite any risky situation (shower…);

x

Implement immediate curative measures such as desinfectation, heat shock, etc…

4

.

7

.

2

W

a

r

m w

at

er

ins

ta

ll

at

ion

The temperature of the outlet at warm water systems

shall

be at least 60

q

C. The identification and assessing

of the risk

should

focus on areas where this could not be reached.

Measures

should

be taken to improve the system (i.e. to increase the temp. setting of the boiler.) Or

measures

should

be taken to control this risk (i.e. the system

shall

be heated up to 60ºC temperature for at

least 20 minutes every week).

Version 04. Original date: 25/05/2012. Version date: 31/12/2014. Valid version only on QMS site. Uncontrolled document when printed.

Procedure prepared by: BOS QHSE Coordinator. Approved by: BOS QHSES Manager. Validated by: BOS Quality Representative

12 / 18